Shrnutí obsahu

Strany 1 - Single Circuit

gForce GTR-410ASingle CircuitAir Cooled, Water/Glycol Cooled7 to 46 kW

Strany 2

10Energy Saver Coil - The Data Aire Energy Saver Coil is built into the system to provide total required capacity. Whenever the incoming water/glycol

Strany 3

11OPTIONS, continuedthe evaporator under full load will maintain pressure on the leaving side of the hot gas bypass valve to keep the valve port close

Strany 4

12MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in kW/hr - gross80° DB/67° WB Total 26,700 3

Strany 5

13MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity 2 2 2 2 - - -Size - inches Dow

Strany 6

14MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 ELECTRICAL SECTION Next Size FanElectrical data based

Strany 7

15MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in Btu/hr - gross80° DB/67° WB Total 27,900 41,30

Strany 8

16MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity 2 2 2 2 - - -Size - inches

Strany 9

17AIR COOLED: Performance data at OPTIONAL airfl ow with remote air cooled condenser MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U

Strany 10

18AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD

Strany 11 - Site Monitoring Devices

19MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity Size - inches Downfl ow 1-16x20x4 1

Strany 13

20AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unitR-410AgForce GT also available in R-407C. Data in a separate b

Strany 14

21AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD

Strany 15

22AIR COOLED: Performance data at OPTIONAL airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD

Strany 16

23MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 FILTER SECTION Quantity Size - inches Downfl ow 1-16x20x

Strany 17

24AIR COOLED: Performance Data at OPTIONAL airfl ow with remote outdoor condensing unitR-410AgForce GT also available in R-407C. Data in a separate b

Strany 18

25AIR COOLED: Performance data at OPTIONAL airfl ow with remote outdoor condensing unitMODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD

Strany 19

26MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CAPACITY in Btu/hr - gross80° DB/67° WB Total 30,000 44

Strany 20

27MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046FILTER SECTION Quantity 2 2 2 2 - - -Size - inches

Strany 21

28WATER COOLED: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.MODEL NUMBER GTWD/U0

Strany 22

29WATER COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CONDENS

Strany 23

3… the pioneer and builder of the most complete line of precision cooling equipmentBack in the late 1960’s and early 70’s with the advancement of the

Strany 24

30WATER COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CAPACI

Strany 25

31WATER COOLED: Performance data at OPTIONAL airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.MODEL NUMBER GTWD/U0

Strany 26

32WATER COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 ELECTRI

Strany 27

33WATER COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CONDEN

Strany 28

34GLYCOL COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 CAPAC

Strany 29

35GLYCOL COOLED: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.MODEL NUMBER GTGD/U0

Strany 30

36GLYCOL COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 ELECT

Strany 31

37GLYCOL COOLED: Performance data at STANDARD airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FLUID

Strany 32

38GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 CAPACI

Strany 33

39GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046FILTER S

Strany 34

4Table of ContentsDesign features ... 7Control sy

Strany 35

40GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046ELECTRIC

Strany 36

41GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FLUID

Strany 37

42AUXILIARY CHILLED WATER: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.Based on 45° F

Strany 38

43AUXILIARY CHILLED WATER: Performance data at OPTIONAL airfl owBased on 45° F entering fl uid temperature - 0% glycol.MODEL NUMBER GT*D/U007 GT*D

Strany 39

44ENERGY SAVER: Performance data at STANDARD airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.Based on 45° F entering fl

Strany 40

45ENERGY SAVER: Performance data at OPTIONAL airfl owR-410AgForce GT also available in R-407C. Data in a separate brochure.Based on 45° F entering fl

Strany 41

46gForce GT DX Downfl ow 7, 11, 14 and 18 kW

Strany 42

47gForce GT DX Upfl ow 7, 11, 14 and 18 kW

Strany 43

48gForce GT DX Downfl ow 28, 35 and 46 kW using Condensing units

Strany 44

49gForce GT DX Upfl ow 28, 35 and 46 kW using Condensing units

Strany 45

5IMPROVED PERFORMANCE andREDUCED MAINTENANCEBackward curved fans discharge air radially allowing for uniform static pressure across the raised fl oor.

Strany 46

50DATA TEMP Air Cooled Condensers, DARC 03 and 05, single circuit

Strany 47

51DATA TEMP Air Cooled Condensers, DARC 06-21, single circuit

Strany 48

52DATA TEMP Air Cooled Condensers, DARC 06-21, single circuit

Strany 49

53DATA TEMP Fluid Coolers, DAFC 06-30

Strany 50

54DATA TEMP Fluid Coolers, DAFC 06-30

Strany 51

55Standard Condenser Electrical Data 208/1/60 208/3/60 460/3/60 Model FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOPDARC 03 4.6/5.8/15 4.6/5.8/15 2.3/2.9/1

Strany 52

56 GUIDE SPECIFICATIONS 7-46 kW DX unitsComputer Room Air Conditioning Units(Floor Mounted, Direct Expansion, 7 to 46 kW)1.01 GENERALA. The

Strany 53

57 GUIDE SPECIFICATIONS 7-46 kW DX unitscoil shall be in a cross circuited or interlaced “A” frame arrangement to allow maximum coil surface

Strany 54

58 GUIDE SPECIFICATIONS 7-46 kW DX unitstype with complete overload protection on all three power lines, internal thermostats for winding pr

Strany 55 - /MCA/MOP

59 GUIDE SPECIFICATIONS 7-46 kW DX units1.08 WATER SENSORUnits shall be provided with one (1) water sensor. The solid state water sensor sha

Strany 56

6INCREASED THERMODYNAMICEFFICIENTIESgForce’s design incorporates rifl ed tubing cool-ing coils. Rifl e tubing is similar to borings in a gun barrel wh

Strany 57

60 GUIDE SPECIFICATIONS 7-46 kW DX unitsE. The following alarm functions shall be monitored and displayed when they occur in addition to enu

Strany 58

61 GUIDE SPECIFICATIONS 7-46 kW DX unitsThe following protocols shall be supported:Modbus RTU, TCP/IP or ASCHII SNMP V1 or V2BACnet IP or M

Strany 59

62 GUIDE SPECIFICATIONS 7-46 kW DX unitsfor fi eld installation and shall include sump, motor, and automatic control. The pumps shall be rate

Strany 60

63 GUIDE SPECIFICATIONS 7-46 kW DX units • Master unit fail safe mode allows slave units to revert their self control modeT. No Water Flow

Strany 61

gForceGT410-3/10

Strany 62

7FRAME AND CABINETThe heliarc welded tubular steel frame provides for maximum strength and ease of access. Side and front panels can be eas-ily opene

Strany 63

8DATA ALARM PROCESSOR-IIIThe Data Alarm Processor-III (DAP™ III) offers the defi nitive answer for precision environmental control. The DAP-III control

Strany 64

9PROTECTIVE and SAFETY FEATURESMetal shell enclosure with sealed front control panel Watch dog timerOpto-coupler signal inputs Protected 24VAC power