13
Water/glycol system piping may include a centrifugal pumps (or pumps for redundancy). Pumps
must be primed before operating per the pump manufacturer’s guidelines.
2.2.1 Field Piping, Glycol System
2.2.2 Connection Sizes, Water/Glycol Cooled Units
Evaporator
Model
Water IN and Out
Connections, O.D.
Evaporator
Model
Water IN and Out
Connections O. D.
DTW/G-02 3/4” DTW/G-08 1-5/8”
DTW/G-03 3/4” DTW/G-10 1-5/8”
DTW/G-04 1-1/8” DTW/G-13 1-5/8”
DTW/G-05 1-1/8”
2.2.3 Connection Sizes, Fluid Coolers
Fluid Cooler
Model
Water IN and OUT
Connections, O.D.
Fluid Cooler
Model
Water IN and OUT
Connections, O.D.
DAFC-06 1-5/8” DAFC-37 2-5/8”
DAFC-07 1-5/8” DAFC-40 2-5/8”
DAFC-09 1-5/8” DAFC-44 2-1/8”
DAFC-11 2-1/8” DAFC-50 2-5/8”
DAFC-15 2-1/8” DAFC-57 2-5/8”
DAFC-17 2-5/8” DAFC-61 2-5/8”
DAFC-21 2-1/8” DAFC-75 2-5/8”
DAFC-24 2-5/8” DAFC-80 2-5/8”
DAFC-28 2-1/8” DAFC-88 2-5/8”
DAFC-30 2-1/8” DAFC-100 2-5/8”